Basic Info.
Application
Construction, Overhead, Underground, Industrial, Power Station, Telecommunication
Voltage
Low and Medium Voltage Cable
Wire Core Material
Bare Copper Wire
Armoring Method
Swa/Sta/ATA/Awa Power Cable
Screen Method
Copper Wire/Copper Tape Power Cable
Printing Method
Heat Printing, Laser Printing, Ink Printing
Standard
BS,IEC,DIN, ASTM, Sans or Other Standard
Transport Package
Wooden Drum, Steel Wooden Drum, Steel Drum
Specification
from 1.5--1000mm2
Product Description
19/33kv Steel Wire Armored Cable XLPE Insulated cable Power CableIt is used to transmit and distribute power in power transmission and distribution systems of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable. Power cables for power networks, underground, outdoors and in cable ducting.
Standard: BS6622, BS EN/IEC 60228,IEC60502.2
Conductor: Class 2 stranded plain copper conductor to BS EN 60228:2005 (previously BS6360)
Conductor screen: Semiconducting material
Insulation: XLPE (Cross-Linked Polyethylene) Type GP8 to BS7655
Insulation Screen: Semi-conducting material
Metallic Screen: Individual and overall copper tape screen to BS6622
Filler: PET (Polyethylene Terephthalate) fibers
Separator: Binding tape
Bedding: PVC (Polyvinyl Chloride) Type TM1 to BS7655
Armoring:Single Core: Aluminium Wire Armoured (AWA)
MultiCore: Steel Wire Armoured (SWA)
Sheath: PVC (Polyvinyl Chloride) Type TM1 to BS7655
Colour: Red or Black
2. Using features :Medium Voltage Power Cable Underground 11kv 15kv 33kv XLPE Power Cable
1. Rated voltage: Uo/U:3.6/6kV, 6/10kV(11kV), 12/20kV(24kV), 19/33kV, 26/35kV(35kV).
2. No. of core: Single-core or three cores.
3. The highest allowed operating temperature of conductor for long-term working is 90oC. In short-circuit (Max. long-term is no more than 5 seconds). The highest temperature for a conductor is no more than 250ºC.
4. D.C. resistance of the conductor complies with the stipulations of 3.6/6kV, 6/10kV(11kV), 12/20kV(24kV), 19/33kV, 26/35kV(35kV).
5. The environment temperature should be no lower than 0oC when lay. Otherwise, it should be preheated.
6. The cable is laid without a horizontal drop limit.
7. Working Frequency Voltage Test: 3.5Uo/5min without puncture.
8. Partial Discharge Test: The discharge volume should be no more than 10pC under 1.73Uo for the cable.
9. Minimum Bending Radius: Single core - Fixed: 15 x overall diameter;3 core - Fixed: 12 x overall diameter
(Single core 12 x overall diameter and 3 core 10 x overall diameter where bands are positioned adjacent to joint or terminations provided that the bending is carefully controlled by the use of a former)
Note: The single-core armored cables are used for the D.C. system only. If used for the A.C. system, the magnetic isolation should be applied to the steel armor wires of non-magnetical materials that should be used.
1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable No.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight |
Al Conductor | Cu Conductor |
No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
3 X 25 | 6.0 | 2.5 | 0.1 | 1.2 | 0.2 | 1.9 | 37.9 | 1.87 | 2.32 |
3 X 35 | 6.9 | 2.5 | 0.1 | 1.3 | 0.5 | 2.0 | 41.5 | 2.10 | 2.73 |
3 X50 | 8.2 | 2.5 | 0.1 | 1.3 | 0.5 | 2.0 | 44.3 | 2.37 | 3.22 |
3 X 70 | 9.7 | 2.5 | 0.1 | 1.4 | 0.5 | 2.1 | 47.9 | 2.77 | 4.00 |
3 X 95 | 11.3 | 2.5 | 0.1 | 1.4 | 0.5 | 2.2 | 51.6 | 3.21 | 4.91 |
3 X 120 | 12.8 | 2.5 | 0.1 | 1.5 | 0.5 | 2.4 | 55.4 | 3.69 | 5.84 |
3 X 150 | 14.2 | 2.5 | 0.1 | 1.5 | 0.5 | 2.5 | 58.6 | 4.15 | 6.85 |
3 X 185 | 15.9 | 2.5 | 0.1 | 1.5 | 0.5 | 2.6 | 62.5 | 4.73 | 8.11 |
3 X 240 | 18.3 | 2.6 | 0.1 | 1.6 | 0.5 | 2.7 | 68.5 | 5.62 | 10.05 |
3 X 300 | 20.4 | 2.8 | 0.1 | 1.7 | 0.5 | 2.9 | 74.5 | 6.55 | 12.11 |
3 X 400 | 23.2 | 3.0 | 0.1 | 1.9 | 0.8 | 3.2 | 83.6 | 8.78 | 15.86 |
3 X 500 | 26.4 | 3.2 | 0.1 | 2.1 | 0.8 | 3.4 | 93.0 | 10.52 | 18.85 |
2)6/10(12)kV,6.35/11(12)kV,,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power CableNo.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight |
Al Conductor | Cu Conductor |
No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
3 X 25 | 6.0 | 3.4 | 0.1 | 1.3 | 0.5 | 2.0 | 43.4 | 2.16 | 2.61 |
3 X 35 | 6.9 | 3.4 | 0.1 | 1.3 | 0.5 | 2.0 | 45.4 | 2.36 | 2.99 |
3 X50 | 8.2 | 3.4 | 0.1 | 1.4 | 0.5 | 2.2 | 48.8 | 2.69 | 3.54 |
3 X 70 | 9.7 | 3.4 | 0.1 | 1.5 | 0.5 | 2.3 | 52.4 | 3.10 | 4.33 |
3 X 95 | 11.3 | 3.4 | 0.1 | 1.5 | 0.5 | 2.4 | 56.1 | 3.56 | 5.26 |
3 X 120 | 12.8 | 3.4 | 0.1 | 1.5 | 0.5 | 2.5 | 59.5 | 4.04 | 6.19 |
3 X 150 | 14.2 | 3.4 | 0.1 | 1.5 | 0.5 | 2.6 | 62.7 | 4.49 | 7.19 |
3 X 185 | 15.9 | 3.4 | 0.1 | 1.6 | 0.5 | 2.6 | 66.6 | 5.12 | 8.49 |
3 X 240 | 18.3 | 3.4 | 0.1 | 1.7 | 0.5 | 2.8 | 72.4 | 5.99 | 10.42 |
3 X 300 | 20.4 | 3.4 | 0.1 | 1.8 | 0.5 | 3.0 | 77.5 | 6.86 | 12.42 |
3 X 400 | 23.2 | 3.4 | 0.1 | 1.9 | 0.8 | 3.2 | 85.4 | 8.97 | 16.05 |
3 X 500 | 26.4 | 3.4 | 0.1 | 2.0 | 0.8 | 3.4 | 93.7 | 10.65 | 19.50 |
3)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power CableNo.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight |
Al Conductor | Cu Conductor |
No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
3 X 25 | 6.0 | 4.5 | 0.1 | 1.4 | 0.5 | 2.1 | 48.6 | 2.53 | 2.98 |
3 X 35 | 6.9 | 4.5 | 0.1 | 1.4 | 0.5 | 2.2 | 50.7 | 2.76 | 3.39 |
3 X50 | 8.2 | 4.5 | 0.1 | 1.5 | 0.5 | 2.3 | 53.9 | 3.10 | 3.95 |
3 X 70 | 9.7 | 4.5 | 0.1 | 1.5 | 0.5 | 2.4 | 57.4 | 3.51 | 4.74 |
3 X 95 | 11.3 | 4.5 | 0.1 | 1.5 | 0.5 | 2.6 | 61.2 | 4.05 | 5.75 |
3 X 120 | 12.8 | 4.5 | 0.1 | 1.6 | 0.5 | 2.6 | 64.7 | 4.56 | 6.72 |
3 X 150 | 14.2 | 4.5 | 0.1 | 1.6 | 0.5 | 2.7 | 67.9 | 5.04 | 7.74 |
3 X 185 | 15.9 | 4.5 | 0.1 | 1.7 | 0.5 | 2.8 | 71.9 | 5.66 | 9.04 |
3 X 240 | 18.3 | 4.5 | 0.1 | 1.8 | 0.5 | 3.0 | 77.7 | 6.56 | 11.00 |
3 X 300 | 20.4 | 4.5 | 0.1 | 1.9 | 0.8 | 3.2 | 84.1 | 8.39 | 13.96 |
3 X 400 | 23.2 | 4.5 | 0.1 | 2.0 | 0.8 | 3.3 | 90.5 | 9.71 | 16.79 |
3 X 500 | 26.4 | 4.5 | 0.1 | 2.1 | 0.8 | 3.5 | 98.8 | 11.45 | 20.57 |
4)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power CableNo.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight |
Al Conductor | Cu Conductor |
No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
3 X 25 | | | | | | | | | |
3 X 35 | 6.9 | 5.5 | 0.1 | 1.5 | 0.5 | 2.4 | 55.6 | 3.14 | 3.77 |
3 X50 | 8.2 | 5.5 | 0.1 | 1.5 | 0.5 | 2.5 | 58.6 | 3.49 | 4.34 |
3 X 70 | 9.7 | 5.5 | 0.1 | 1.5 | 0.5 | 2.6 | 62.1 | 3.93 | 5.16 |
3 X 95 | 11.3 | 5.5 | 0.1 | 1.6 | 0.5 | 2.6 | 65.7 | 4.46 | 6.16 |
3 X 120 | 12.8 | 5.5 | 0.1 | 1.7 | 0.5 | 2.7 | 69.4 | 5.00 | 7.15 |
3 X 150 | 14.2 | 5.5 | 0.1 | 1.7 | 0.5 | 2.8 | 72.6 | 5.49 | 8.19 |
3 X 185 | 15.9 | 5.5 | 0.1 | 1.8 | 0.5 | 3.0 | 76.9 | 6.16 | 9.53 |
3 X 240 | 18.3 | 5.5 | 0.1 | 1.9 | 0.8 | 3.2 | 83.9 | 7.87 | 12.31 |
3 X 300 | 20.4 | 5.5 | 0.1 | 2.0 | 0.8 | 3.2 | 88.6 | 8.96 | 14.52 |
3 X 400 | 23.2 | 5.5 | 0.1 | 2.1 | 0.8 | 3.5 | 95.4 | 10.35 | 17.43 |
3 X 500 | 26.4 | 5.5 | 0.1 | 2.2 | 0.8 | 3.7 | 103.7 | 12.45 | 20.23 |
5)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power CableNo.X Nominal Cross Section of Conductor | Nominal Diameter of Conductor | Nominal Thickness of Insulation | Nominal Thickness of Copper Tape Screen | Nominal Thickness of Inner Sheath | Nominal Thickness of Steel Tape Armouring | Nominal Thickness of PVC Sheath | Approx. Overall Diameter | Approx. Weight |
Al Conductor | Cu Conductor |
No. X mm2 | mm | mm | mm | mm | mm | mm | mm | kg/m | kg/m |
3 X 25 | | | | | | | | | |
3 X 35 | | | | | | | | | |
3 X50 | 8.2 | 8.0 | 0.1 | 1.7 | 0.5 | 2.8 | 70.4 | 4.56 | 5.41 |
3 X 70 | 9.7 | 8.0 | 0.1 | 1.7 | 0.5 | 2.9 | 73.9 | 5.04 | 6.26 |
3 X 95 | 11.3 | 8.0 | 0.1 | 1.8 | 0.5 | 3.0 | 77.7 | 5.62 | 7.32 |
3 X 120 | 12.8 | 8.0 | 0.1 | 1.9 | 0.8 | 3.2 | 82.8 | 6.99 | 9.15 |
3 X 150 | 14.2 | 8.0 | 0.1 | 1.9 | 0.8 | 3.2 | 85.8 | 7.56 | 10.26 |
3 X 185 | 15.9 | 8.0 | 0.1 | 2.0 | 0.8 | 3.3 | 89.9 | 8.30 | 11.67 |
3 X 240 | 18.3 | 8.0 | 0.1 | 2.1 | 0.8 | 3.5 | 95.7 | 9.36 | 13.79 |
3 X 300 | 20.4 | 8.0 | 0.1 | 2.2 | 0.8 | 3.6 | 100.6 | 10.51 | 16.07 |
3 X 400 | 23.2 | 8.0 | 0.1 | 2.3 | 0.8 | 3.8 | 107.2 | 11.99 | 19.07 |
3 X 500 | 26.4 | 8.0 | 0.1 | 2.4 | 0.8 | 4.0 | 120.1 | 14.15 | 23.85 |
Conductors on OHTL(overhead transmission line): AAC, AAAC, ACSR, ACS wires, Aluminum Clad Steel Conductor(Alumoweld), Copperweld cable, Galvanized Steel Cable(Stay wires)
Optical Fiber Ground Conductors: Al Clad PBT tube OPGW, Al clad stainless steel tube OPGW, Layer stranded OPGW, SSLT Fiber optic unit, OPPC, ADSS
Insulated conductors for power distribution system: Aerial bundle cables (ABC Cables), 8000 series Alloy Concentric cables, Airdac cable, Twiested insulated cables, Preassembled self-supporting cables, CAAI, 15kV, 25kV covered conductors, URD cables
Main XLPE insulated Power cables, EPR insulated Power cables and PVC insulated Power cables up to voltage 36kV
If some of our items are interested to you, please dont hesitate to contact with us!
Address:
No. 2, Floor 1, East Unit 1, Building 29, Yangguangjiayuan, No. 99 Guoji Road, Zhengzhou, Henan, China
Business Type:
Manufacturer/Factory, Trading Company
Business Range:
Electrical & Electronics, Lights & Lighting
Management System Certification:
ISO 9001, ISO 14001
Company Introduction:
Henan Hoham Cable Co., Ltd. is the representative exporter for cable products from China Aerospace Electric Group (hereinafter referred to as AEG Group). Hoham Cable is located in Zhengzhou, the capital of Henan Province in central China, also the city with one of the biggest aluminum stock reserve in China and expedite transportation network. Starting from the raw aluminum procurement department of the AEG group, now Hoham Cable has developed into an independent company with good reputation and experience in international market.
With relentless pursuit of quality and years of unremitting efforts in market, Hoham cable have achieved sound cooperation and widely compliments from the clients all over the world by superior quality, reasonable price and sincere services.
Outfitted with the latest generation of technologies. Facilities, equipment and the finest engineering team, . The product range of Hoham Cable covers more than 1400 types of cables and wires in scores of categories. Our products with reliable quality and strong international competitiveness mainly covers:
Conductors on OHTL(overhead transmission line): AAC, AAAC, ACSR, ACS wires, Aluminum Clad Steel Conductor(Alumoweld), Copperweld cable, Galvanized Steel Cable(Stay wires)
Optical Fiber Ground Conductors: Al Clad PBT tube OPGW, Al clad stainless steel tube OPGW, Layer stranded OPGW, SSLT Fiber optic unit, OPPC, ADSS
Insulated conductors for power distribution system: Aerial bundle cables (ABC Cables), 8000 series Alloy Concentric cables, Airdac cable, Twiested insulated cables, Preassembled self-supporting cables, CAAI, 15kV, 25kV covered conductors, URD cables
Main XLPE insulated Power cables, EPR insulated Power cables and PVC insulated Power cables up to voltage 36kV
Our products can conform to most general international standards such as GB, JB, IEC, ASTM, BS, SNAS, DIN, JIS, NF, AS/NZS and so forth. Also we can produce based on customers′ requirements and specifications. Our products have already been verified to conform to the certification of China Compulsory Product Certification (CCC), PCCC, CQC Mark Certification, MA and others from China and abroad.
Based on outstanding quality and professional service, Hoham Cable has been making every effort to develop and expand the domestic and international market. We had established sound business relationship with clients all over the world, exported products to the clients from Europe, Australia, Middle East, Africa, South Asia, North America, Central and South America, and obtained the clients′ trust and compliment.
With great leadership and high-end technology, Hoham cable had offered the safe, effective and excellent solutions to electrical sectors in different countries and our clients had benefited from the partnership and cooperation. In future, we will strictly adhere to our commitment, carry on the past and open a way for future. And we will closely follow the trend of scientific and technical development of wire and cable industry and strive to be the best manufacture to global market.
Together with you, surely we will achieve more successes!